Dwellings |
Buildings other than dwellings |
| Country |
New / Existing |
New / Existing |
| England/Wales |
Minimum equivalent area of 5000mm² in each habitable room |
CIBSE Application Manual AM10 (new) - Up to 10m² floor area = 2500mm²/over 10m² = 250mm² per 1m² of floor area |
| Scotland |
12000mm² or average of 11000mm/room with 11000mm² min for habitable rooms |
Min 4000mm² + 400mm²/m² up to 10m² of floor area or 400mm²/m² above 10m² of floor area |
| Northern Ireland |
8000mm² or average of 6000mm²/room |
4000mm² up to 10m² of floor area or 400mm²/m² above 10m² of floor area |
|---|
| |
Dwellings Buildings other than dwellings |
| Country |
New / Existing |
New / Existing |
| England/Wales |
1/20 of floor area >30 degrees / 1/20 floor area <30 degree |
Various depending on type of building |
| Scotland |
1/30 of floor area |
1/30 of floor area |
| Northern Ireland |
1/20 of floor area |
1/20 of floor area |
|---|
*30 degrees is the opening angle of the sash and applies to all windows
"The difference in free and equivalent background ventilation areas is that the equivalent area has a default value included to allow for the effectiveness of the ventilator whilst the free area is just the total area of the vent."